Oferta
| Color / Pattern |
|
| Power Source |
|
| Controller Design |
|
The Yokogawa ADM51T is a Contact Output Module designed for distributed control systems, supporting 16 transistor output points with flexible pulse width and time‑proportional control functions. It provides robust ON/OFF status output, pulse generation, and per‑point insulation for reliable field operation.
Model: ADM51T
Brand: Yokogawa
Product Type: Contact Output Module
Suffix Codes:
‑1: Reset action during on‑line maintenance
‑2: Hold action during on‑line maintenance
No. of I/O Points: 16 points
Output Signal: Transistor contact
Contact Rating: Resistive/Inductive load: 30 V DC, ≤100 mA
Pulse Width: 0.1 to 7200 s (settable in pulse‑type mode)
Pulse Width Resolution: 20 ms
Current Consumption: ≤600 mA (5.0 V DC)
Functions:
Status output
Pulse type output
Pulse width output
Time proportional ON/OFF
ON/OFF status output function
One‑shot pulse width output function
Abnormal detection mode with configurable detection time/output mode
Signal Insulation: Each point individually insulated
Mounting Method: Installed in the I/O module nest
Signal Connection: Terminal connection with M4 screws; KS2/KS3 or KS9/KS10 cable supported
CPU Halt/Bus Termination Status: Detection time and output mode configurable
16 transistor outputs for flexible control.
Pulse width control adjustable from 0.1 to 7200 seconds.
Time proportional ON/OFF for precise process regulation.
Per‑point insulation ensures reliability and isolation.
Abnormal detection mode configurable for fault handling.
Q: How many outputs does the ADM51T provide? A: It supports 16 transistor contact outputs.
Q: What is the maximum load rating per channel? A: Each channel supports up to 30 V DC, 100 mA.
Q: Can the module generate one‑shot pulses? A: Yes, it supports one‑shot pulse width output functions.
Q: What insulation method is used? A: Each output point is individually insulated.
Install the ADM51T securely into the I/O module nest.
Connect signals to the nest terminal using M4 screws with proper torque.
Use KS2/KS3 or KS9/KS10 cables for wiring.
Maintain shield grounding at a single point to prevent ground loops.
Configure pulse width, time proportional control, and abnormal detection via system software before commissioning.

Despacho rápido desde nuestro inventario global para reducir el tiempo de inactividad y garantizar operaciones ininterrumpidas.
Todas las piezas provienen de fabricantes acreditados y se someten a exhaustivos controles de calidad.
Amplio stock de repuestos para automatización industrial y piezas descatalogadas, listas para su envío inmediato.
Todos los productos —incluidos los artículos obsoletos— están cubiertos por una garantía de 12 meses y una garantía de devolución de 30 días.
Todos los nombres de productos, marcas comerciales, marcas y logotipos mencionados en este sitio web son propiedad de sus respectivos dueños. Estos nombres y marcas comerciales se utilizan únicamente con fines de identificación y referencia. Somos un proveedor independiente de piezas de repuesto para automatización industrial. No somos un distribuidor autorizado, concesionario o representante de ningún fabricante. Los productos suministrados pueden incluir inventario excedente o artículos sin usar. No reclamamos ninguna afiliación o respaldo por parte de los fabricantes originales.