Configured for high-accuracy thermocouple and millivolt signal measurement in Yokogawa DCS systems, the Yokogawa AST143-S00 (AST143 TC/mV Input Module) provides direct physical/electrical execution. It processes up to 16 input channels and transmits conditioned data across the system backplane with minimal propagation delay.
The base module designation AST143 defines the 16-channel thermocouple and millivolt input processing hardware architecture. The -S00 suffix specifies the standard hardware option set, incorporating built-in isolation and standard system integration features without custom barrier modifications.
| Parameter | Specification |
|---|---|
| Model | AST143-S00 |
| Brand | Yokogawa |
| Origin | Japan / Singapore |
| Weight | 0.30 kg |
| Dimensions | 120 mm x 100 mm x 39 mm (W x H x D) |
| Operating Temp | -20 to 70 deg C |
| Power Consumption | 150 mA at 5 VDC, 80 mA at 24 VDC |
| Number of Channels | 16 |
| Input Signal Types | Thermocouple (TC), Millivolt (mV) |
| Input Ranges | TC: -200 to 1500 deg C; RTD: -200 to 800 deg C; Thermistor: -50 to 150 deg C |
| Output | 4 to 20 mA |
| Accuracy | +/-0.2% of span; TC: +/-40 uV, mV: +/-80 uV at 23 deg C |
| Communication Protocol | HART |
| Power Supply | 24 VDC +/-10% |
| Input Resistance | >= 1 Mohm (Power ON/OFF) |
| Data Update Period | 10 ms |
| Withstanding Voltage | 1500 VAC between circuits and channels |
Q: Can the AST143-S00 module be inserted or removed while the 24 VDC field supply remains active?
A: Yes. The hardware design allows live insertion and removal from the backplane, provided that field wiring circuits adhere to localized hazardous area safety precautions.
Q: What is the input impedance behavior of the module when backplane power is removed?
A: The input resistance remains >= 1 Mohm in both Power ON and Power OFF states, preventing loading effects on active field measurement loops.
Mount the AST143-S00 securely into the designated slot on the field control station baseplate, ensuring the locking mechanism fully engages. Route thermocouple extension wires and millivolt signal leads separately from high-voltage AC cables to prevent electromagnetic coupling. Connect signal cable shielding to a single dedicated functional earth point. Verify that the ambient operating temperature inside the cabinet remains within -20 to 70 deg C to maintain measurement drift within the specified limits.

إرسال سريع من مخزوننا العالمي لتقليل وقت التوقف وضمان العمليات دون انقطاع.
جميع الأجزاء مصدرها شركات مصنعة ذات سمعة طيبة وتخضع لفحوصات جودة شاملة.
مخزون واسع النطاق من الأتمتة الصناعية والأجزاء المتوقفة، جاهزة للشحن الفوري.
يتم تغطية كل منتج - بما في ذلك المنتجات القديمة - بضمان لمدة 12 شهرًا وضمان إرجاع لمدة 30 يومًا.
جميع أسماء المنتجات والعلامات التجارية والشعارات المذكورة في هذا الموقع هي ملك لأصحابها. تُستخدم هذه الأسماء والعلامات التجارية لأغراض التعريف والمراجع فقط. نحن مورد مستقل لقطع غيار الأتمتة الصناعية. لسنا موزعًا أو تاجرًا أو ممثلاً معتمدًا لأي مصنع. قد تشمل المنتجات الموردة مخزونًا فائضًا أو عناصر غير مستخدمة. لا ندعي أي انتماء أو تأييد من قبل المصنعين الأصليين.