The Honeywell TK-OAV081, also cataloged as the OAV081 analog output module, operates as a dedicated hardware component for current and voltage signal generation within Honeywell process control systems.
| Parameter | Specification |
|---|---|
| Model | TK-OAV081 |
| Brand | Honeywell |
| Origin | Honeywell process control platforms |
| Weight | 0.5 kg (Shipping weight: 2 kg) |
| Dimensions | Not specified in provided data |
| Operating Temp | Standard industrial ambient range |
| Power Consumption | 6.9 W max |
| Core Function | 8-point analog output (current/voltage) |
| Voltage Output Range | ±10.4 V |
| Current Output Range | 0 to 21 mA |
| Resolution | 320 µV per count (Voltage), 650 nA per count (Current) |
| Accuracy | Better than 0.05% at 25 deg C |
| Isolation | 2550 VDC user-to-system, tested 1 s |
| Protection | Overvoltage protection, short-circuit current limiting |
| Update Rate | 25 ms for all channels |
| Settling Time | <2 ms to 95% final value |
| Connection | TC-TBNH, 20-position terminal block |
The TK-OAV081 supports integration with Honeywell environments utilizing 4-20 mA HART loop protocol, enabling simultaneous analog signal transmission and diagnostic communication. Channel-to-channel isolation ensures that voltage and current outputs remain independent, minimizing interference across the eight channels. Cold junction compensation (CJC) is applied for stability in varying ambient conditions.
Q: Can the TK-OAV081 drive high-resistance loads? A: Yes, voltage outputs can drive >2000 Ω loads, while current outputs support up to 750 Ω.
Q: What is the module’s behavior under short-circuit conditions? A: Outputs are electronically limited to 21 mA or less, preventing damage during open or short circuit events.
Q: How does temperature drift affect accuracy? A: Typical offset drift is 50 µV/deg C (voltage) and 100 nA/deg C (current), with gain drift limited to 25 ppm/deg C (voltage) and 50 ppm/deg C (current).
Mount the module securely in the designated chassis slot.
Connect TC-TBNH 20-position terminal block with proper torque to avoid loose contacts.
Ground shielding at a single point to reduce RFI susceptibility.
Verify load resistance compatibility before energizing outputs.
Maintain clearance for airflow to dissipate 6.9 W maximum heat.

إرسال سريع من مخزوننا العالمي لتقليل وقت التوقف وضمان العمليات دون انقطاع.
جميع الأجزاء مصدرها شركات مصنعة ذات سمعة طيبة وتخضع لفحوصات جودة شاملة.
مخزون واسع النطاق من الأتمتة الصناعية والأجزاء المتوقفة، جاهزة للشحن الفوري.
يتم تغطية كل منتج - بما في ذلك المنتجات القديمة - بضمان لمدة 12 شهرًا وضمان إرجاع لمدة 30 يومًا.
جميع أسماء المنتجات والعلامات التجارية والشعارات المذكورة في هذا الموقع هي ملك لأصحابها. تُستخدم هذه الأسماء والعلامات التجارية لأغراض التعريف والمراجع فقط. نحن مورد مستقل لقطع غيار الأتمتة الصناعية. لسنا موزعًا أو تاجرًا أو ممثلاً معتمدًا لأي مصنع. قد تشمل المنتجات الموردة مخزونًا فائضًا أو عناصر غير مستخدمة. لا ندعي أي انتماء أو تأييد من قبل المصنعين الأصليين.