The GE IS200TBAIH1CDD, also cataloged as the IS200TBAIH1CDD Analog Input Terminal Board, is part of the Mark VIe control system. It provides 10 analog input channels and 2 analog output channels, supporting multiple transmitter wiring types and configurable current ranges. The board is designed with surface-mount technology and integrates noise suppression circuitry for surge and high-frequency interference protection.
Part Number: IS200TBAIH1CDD
Manufacturer: General Electric
Series: Mark VIe
Board Type: Analog Input Terminal Board
Country of Origin: United States
Number of Channels: 12 (10 inputs, 2 outputs)
Input Span: 1-5 VDC transmitters
Input Voltage Range: 3.3 V to 5 VDC
Maximum Lead Resistance: 15 Ω
Synchronization Accuracy: ±1 ns
Clock Frequency: Up to 200 MHz
Operating Temperature Range: 30 to 65 deg C
Dimensions: 10.16 cm wide x 33.02 cm high
Mounting Type: Surface-mount technology (SMT)
Manual Reference: GEH6721D
The IS200TBAIH1CDD integrates into Mark VIe racks with deterministic communication over Profinet or EtherNet/IP. Input signals are distributed across R, S, and T channels in TMR configurations, while outputs combine currents from redundant drivers through a shunt for regulation. Synchronization accuracy of ±1 ns and clock frequencies up to 200 MHz ensure precise timing alignment across redundant paths. Firmware flash compatibility allows in-system updates without disrupting analog signal handling.
Q: Can the IS200TBAIH1CDD outputs be configured beyond 20 mA? A: Yes. The first output supports up to 200 mA when configured accordingly.
Q: How are signals managed in TMR applications? A: Inputs are distributed to three connectors for R, S, and T controls, while outputs combine currents from three drivers and regulate via a shunt.
Q: What wiring types are supported for analog inputs? A: Two-wire, three-wire, four-wire, and externally powered transmitters are supported, along with ±5 V and ±10 VDC voltage inputs.
Wire 10 inputs and 2 outputs directly to the two I/O terminal blocks mounted on the board.
Each terminal block supports 24 terminals with #12 AWG wire capacity.
Secure terminal blocks with two screws per block.
Use shield terminal attachment points adjacent to each block for grounding.
Ensure proper routing and shielding of cables to minimize interference.
Confirm connector engagement for simplex (JR1) or TMR (JR1, JR2, JR3) configurations.

إرسال سريع من مخزوننا العالمي لتقليل وقت التوقف وضمان العمليات دون انقطاع.
جميع الأجزاء مصدرها شركات مصنعة ذات سمعة طيبة وتخضع لفحوصات جودة شاملة.
مخزون واسع النطاق من الأتمتة الصناعية والأجزاء المتوقفة، جاهزة للشحن الفوري.
يتم تغطية كل منتج - بما في ذلك المنتجات القديمة - بضمان لمدة 12 شهرًا وضمان إرجاع لمدة 30 يومًا.
جميع أسماء المنتجات والعلامات التجارية والشعارات المذكورة في هذا الموقع هي ملك لأصحابها. تُستخدم هذه الأسماء والعلامات التجارية لأغراض التعريف والمراجع فقط. نحن مورد مستقل لقطع غيار الأتمتة الصناعية. لسنا موزعًا أو تاجرًا أو ممثلاً معتمدًا لأي مصنع. قد تشمل المنتجات الموردة مخزونًا فائضًا أو عناصر غير مستخدمة. لا ندعي أي انتماء أو تأييد من قبل المصنعين الأصليين.