أُوكَازيُون
أُوكَازيُون
| Color / Pattern |
|
| Power Source |
|
| Communication Protocols |
|
| Controller Design |
|
Configured for high-speed multi-winding transformer management and phase differential protection within automated utility substations, the GE Multilin T35-U03-HKH-F8L-H6P-M8N-P6P-U6C-WXX (T35 Transformer Protection System) provides direct physical/electrical execution. It functions as an integrated, modular protective relay platform that processes multi-phase analog waveforms and executes automated high-speed trip outputs based on configurable current restraint algorithms.
| Parameter | Specification |
|---|---|
| Model | T35-U03-HKH-F8L-H6P-M8N-P6P-U6C-WXX |
| Brand | GE (General Electric / Multilin) |
| Series | Universal Relay (UR) Series / T35 |
| Origin | Canada (CA) |
| Weight | Approx. 4.1 kg (9.0 lbs) net mass |
| Dimensions | 4U standard 19-inch rack-mount horizontal chassis assembly |
| Operating Temp | -40 to +70 deg C (-40 to +158 deg F) continuous rating |
| Mounting Orientation | Horizontal layout configuration (Standard 19-inch rack mount) |
| User Interface | Front-panel vertical execution layout with alphanumeric display |
| AC Sensing Array | Phase/ground current transformer (CT) and voltage transformer (VT) matrix |
| Digital I/O | Configurable discrete digital input channels and electromechanical output relays |
| Network Interfacing | High-speed Ethernet module supporting serial and fiber link channels |
| Protocol Capabilities | Modbus RTU, Modbus TCP/IP, DNP3, and IEC 61850 protocol profiles |
Q: How does the internal processor prevent false tripping during high-magnitude transformer inrush current spikes?
A: The digital signal processors compute discrete Fourier transforms (DFT) to continuously analyze current waveforms. During transformer energization, if the 2nd harmonic vector ratio crosses the programmed percentage limit relative to the fundamental 50/60 Hz frequency, the relay determines an inrush condition is present and blocks the fast differential element (87T) to suppress an uncommanded trip.
Q: Can an individual hardware or I/O card module be hot-swapped while the main chassis control power is active?
A: No. The parallel backplane pins and multi-point terminal block sockets lack isolated current-limiting gates for live card insertion. Pulling or sliding hardware modules into an active chassis can cause backplane data parity exceptions, interrupt critical trip sensing paths, or damage delicate solid-state elements via inductive voltage spikes.

إرسال سريع من مخزوننا العالمي لتقليل وقت التوقف وضمان العمليات دون انقطاع.
جميع الأجزاء مصدرها شركات مصنعة ذات سمعة طيبة وتخضع لفحوصات جودة شاملة.
مخزون واسع النطاق من الأتمتة الصناعية والأجزاء المتوقفة، جاهزة للشحن الفوري.
يتم تغطية كل منتج - بما في ذلك المنتجات القديمة - بضمان لمدة 12 شهرًا وضمان إرجاع لمدة 30 يومًا.
جميع أسماء المنتجات والعلامات التجارية والشعارات المذكورة في هذا الموقع هي ملك لأصحابها. تُستخدم هذه الأسماء والعلامات التجارية لأغراض التعريف والمراجع فقط. نحن مورد مستقل لقطع غيار الأتمتة الصناعية. لسنا موزعًا أو تاجرًا أو ممثلاً معتمدًا لأي مصنع. قد تشمل المنتجات الموردة مخزونًا فائضًا أو عناصر غير مستخدمة. لا ندعي أي انتماء أو تأييد من قبل المصنعين الأصليين.