أُوكَازيُون
أُوكَازيُون
Configured for low‑voltage DC supply in Universal Relay (UR) systems, the GE Multilin UR RLH (UR‑RLH power‑supply module) provides regulated 24–48 VDC input conversion for relay electronics, dry‑contact inputs, and the integrated battery circuit. The module includes a form‑C critical‑failure relay that de‑energizes upon loss of control power or detection of a major self‑test fault.
| Parameter | Specification |
|---|---|
| Model | UR‑RLH |
| Brand | GE Multilin |
| Origin | Not specified (GE Multilin standard manufacturing) |
| Weight | approx. 2 lb 2 oz |
| Dimensions | approx. 6.5 in L × 6.5 in W × 1.75 in H |
| Operating Temp | Not specified (UR‑series ambient norms) |
| Power Consumption | Not specified (low‑range DC supply) |
| Voltage Range | 24–48 VDC nominal (LO‑range) |
| Output Capability | Powers relay electronics and dry‑contact inputs |
| Software Support | EnerVista UR |
| Isolation Voltage | 2000 VAC (second‑generation modules) |
| Battery Function | Integrated relay battery located within module |
| Critical Failure Relay | Form‑C device; energized only when boot and self‑tests pass |
UR‑series power‑supply modules participate indirectly in backplane communication by stabilizing voltage rails used by CPU, CT/VT, I/O, and communication modules. The UR‑RLH’s LO‑range design maintains consistent rail behavior under varying DC input conditions, preventing timing drift in backplane bus arbitration. Firmware flash operations on CPU modules require stable rail voltage; therefore, the UR‑RLH’s regulated output ensures deterministic flash‑write cycles and prevents brownout‑related corruption during upgrades.
Q: Can the UR‑RLH be hot‑swapped while the relay remains energized? A: No. Control power must be fully removed before extracting or inserting the module to avoid relay shutdown and critical‑failure relay transitions.
Q: Does the UR‑RLH impose any backplane current limitations? A: The module supplies regulated DC rails; current draw is defined by installed modules. The UR‑RLH does not restrict backplane loading beyond its rated output capability.
Q: Is the UR‑RLH interchangeable with UR‑RH or UR‑SH modules? A: It is a second‑generation LO‑range supply. UR‑SH modules are third‑generation replacements but mixing generations in redundant configurations is not recommended.

إرسال سريع من مخزوننا العالمي لتقليل وقت التوقف وضمان العمليات دون انقطاع.
جميع الأجزاء مصدرها شركات مصنعة ذات سمعة طيبة وتخضع لفحوصات جودة شاملة.
مخزون واسع النطاق من الأتمتة الصناعية والأجزاء المتوقفة، جاهزة للشحن الفوري.
يتم تغطية كل منتج - بما في ذلك المنتجات القديمة - بضمان لمدة 12 شهرًا وضمان إرجاع لمدة 30 يومًا.
جميع أسماء المنتجات والعلامات التجارية والشعارات المذكورة في هذا الموقع هي ملك لأصحابها. تُستخدم هذه الأسماء والعلامات التجارية لأغراض التعريف والمراجع فقط. نحن مورد مستقل لقطع غيار الأتمتة الصناعية. لسنا موزعًا أو تاجرًا أو ممثلاً معتمدًا لأي مصنع. قد تشمل المنتجات الموردة مخزونًا فائضًا أو عناصر غير مستخدمة. لا ندعي أي انتماء أو تأييد من قبل المصنعين الأصليين.