The GE IS200TRLYH1B, also cataloged as the IS200TRLYH1B Relay Output Terminal Board, is part of the Mark VIe turbine control platform. It provides relay‑based discrete outputs with TMR contact voting, combining R, S, and T relay sections to form voted Form A contacts for high‑integrity trip and control functions. The board supports 12 voted relay outputs using a total of 36 sealed relays.
Part Number: IS200TRLYH1B
Manufacturer: General Electric
Series: Mark VIe
Product Type: Relay Output Terminal Board
Number of Channels: 16 (board-level), 12 TMR‑voted outputs
Relay Type: SPDT
Relay Contact Rating: 10 A
Input Voltage Range: 12 V, 24 V
Relay Switching Current: Max 10 A
Analog Outputs: 0-20 mA
Output Resolution: 12‑bit
Output Impedance: 10 Ohm
Mounting Type: DIN rail
Technology: Surface‑mount
Size: 17.8 cm wide x 33.02 cm
Operating Temperature: -30 to 65 deg C
Country of Origin: United States
Manual Reference: GEH‑6721D
Within Mark VIe architectures, the IS200TRLYH1B interfaces through deterministic backplane communication. Relay commands from the controller are distributed to R, S, and T sections, where TMR logic performs contact voting. Firmware flash compatibility ensures coordinated updates across relay sections without interrupting output integrity. I/O density scaling allows the TRLY board to integrate into simplex or TMR racks with consistent timing behavior.
Q: How many relays are used to form each voted output? A: Three relays—one from each R, S, and T section—are combined to form a single Form A voted output.
Q: Can the IS200TRLYH1B be hot‑swapped? A: No. The board requires system de‑energization before removal or insertion to maintain relay integrity and prevent unintended output transitions.
Q: What voltages can be applied to the relay contacts? A: The relay contacts support 24/125 VDC or 115 VAC, depending on system wiring.
Mount the board on a DIN rail with full connector engagement to the Mark VIe rack.
Ensure proper routing of discrete output wiring to avoid induced noise from high‑current conductors.
Maintain separation between analog and relay wiring to reduce interference.
Verify correct polarity and voltage rating before energizing relay circuits.
In TMR systems, confirm all three relay sections (R, S, T) are connected for proper voting behavior.
Use shielded wiring where required and ground shields at a single point to prevent ground loops.

إرسال سريع من مخزوننا العالمي لتقليل وقت التوقف وضمان العمليات دون انقطاع.
جميع الأجزاء مصدرها شركات مصنعة ذات سمعة طيبة وتخضع لفحوصات جودة شاملة.
مخزون واسع النطاق من الأتمتة الصناعية والأجزاء المتوقفة، جاهزة للشحن الفوري.
يتم تغطية كل منتج - بما في ذلك المنتجات القديمة - بضمان لمدة 12 شهرًا وضمان إرجاع لمدة 30 يومًا.
جميع أسماء المنتجات والعلامات التجارية والشعارات المذكورة في هذا الموقع هي ملك لأصحابها. تُستخدم هذه الأسماء والعلامات التجارية لأغراض التعريف والمراجع فقط. نحن مورد مستقل لقطع غيار الأتمتة الصناعية. لسنا موزعًا أو تاجرًا أو ممثلاً معتمدًا لأي مصنع. قد تشمل المنتجات الموردة مخزونًا فائضًا أو عناصر غير مستخدمة. لا ندعي أي انتماء أو تأييد من قبل المصنعين الأصليين.