أُوكَازيُون
أُوكَازيُون
Configured for PWM‑based control power generation and contactor drive functions in EX2000 excitation networks, the GE IS200PSCDG1ADB (IS200PSCDG1ADB power supply / contactor driver board) provides regulated low‑voltage distribution, isolated auxiliary supplies, and DC link‑derived contactor control power for LDCC, TCCB, gate driver, and SHVI/SHVM subsystems.
| Parameter | Specification |
|---|---|
| Model | IS200PSCDG1ADB |
| Brand | General Electric |
| Origin | United States |
| Weight | 2 lbs |
| Dimensions | 16.2 cm high x 8.6 cm |
| Operating Temp | 0 to 70 deg C |
| Storage Temp | -40 to 80 deg C |
| Power Consumption | Not specified |
| Product Type | PWM Power Supply / Contactor Driver Board |
| Series | EX2000 |
| Microprocessor | Intel Celeron 300 MHz |
| Memory | 32 MB DRAM |
| Operating System | QNX |
| Programming | Boolean |
| Ethernet Interface | 10BaseT / 100BaseTX |
| Voltage Range | 14 to 32 V dc |
| Max Load Current | 125 V dc |
| Max Lead Resistance | 15 ohm |
| Technology | Surface mount |
| Core Function | DC link‑derived control power generation, isolated auxiliary supplies, contactor coil drive |
| Manual | GEI‑100241 |
As an EX2000 subsystem board, PSCD aligns with deterministic backplane timing used for excitation control sequencing. The board’s processor executes Boolean logic blocks stored in firmware flash, defining supply enable states, contactor permissive logic, and distribution timing for ±24 V, ±15 V, +5 V, and isolated 70 V dc outputs. Compatibility requires matched firmware revisions across LDCC and TCCB modules; mismatches may inhibit relay K1/K86 control or disrupt auxiliary supply availability. Ethernet communication through the secondary 10BaseT/100BaseTX interface follows deterministic update cycles for diagnostic retrieval.
Q: Can the IS200PSCDG1ADB be replaced while the exciter remains energized? A: No. The board must be installed or removed only when the EX2000 system is de‑energized to avoid undefined supply states and contactor coil activation.
Q: How does the board manage isolated auxiliary supplies? A: High‑frequency transformers generate isolated 70 V dc and SHVI/SHVM supplies. These outputs are filtered and routed through dedicated connectors for downstream modules.
Q: What determines the enable state of the MDA contactor? A: An optically coupled signal, logically parallel to relay K1, controls the MDA contactor. Relay K86 provides the permissive path and drops out immediately during emergency stop conditions.

إرسال سريع من مخزوننا العالمي لتقليل وقت التوقف وضمان العمليات دون انقطاع.
جميع الأجزاء مصدرها شركات مصنعة ذات سمعة طيبة وتخضع لفحوصات جودة شاملة.
مخزون واسع النطاق من الأتمتة الصناعية والأجزاء المتوقفة، جاهزة للشحن الفوري.
يتم تغطية كل منتج - بما في ذلك المنتجات القديمة - بضمان لمدة 12 شهرًا وضمان إرجاع لمدة 30 يومًا.
جميع أسماء المنتجات والعلامات التجارية والشعارات المذكورة في هذا الموقع هي ملك لأصحابها. تُستخدم هذه الأسماء والعلامات التجارية لأغراض التعريف والمراجع فقط. نحن مورد مستقل لقطع غيار الأتمتة الصناعية. لسنا موزعًا أو تاجرًا أو ممثلاً معتمدًا لأي مصنع. قد تشمل المنتجات الموردة مخزونًا فائضًا أو عناصر غير مستخدمة. لا ندعي أي انتماء أو تأييد من قبل المصنعين الأصليين.