The Yokogawa ADM52T-2, also cataloged as the ADM52T-2 (ADT32) Digital Contact Output Module, operates as a dedicated hardware component for binary state actuation within CENTUM CS/VP DCS and ProSafe-RS SIS platforms. Configured as a 32-channel dry contact relay-based interface, this single-slot module switches external control circuits for solenoids, interlock relays, and status indicator fields. It executes output state transitions natively at the subrack tier to maintain system interlocks parallel to master processor execution cycles.
| Parameter | Specification |
|---|---|
| Model | ADM52T-2 (ADT32) |
| Brand | Yokogawa |
| Origin | Japan |
| Weight | 1.36 kg |
| Dimensions | 30 mm x 130 mm x 150 mm |
| Product Type | Digital Contact Output Module |
| Channel Density | 32 independent discrete contact outputs |
| Output Contact Type | Dry contact relay-based outputs |
| Nominal Operational Voltage | 24 VDC |
| Operational Voltage Range | 12 VDC to 30 VDC |
| Isolation Barrier | >=500 VDC between channels and internal system logic |
| Hardware Response Time | <10 ms output signal state actuation transition |
| System Compatibility | Yokogawa CENTUM CS/VP and ProSafe-RS architectures |
Q: What specific hardware behaviors manifest if an external 24 VDC control loop encounters a short circuit at the ADM52T-2 terminal pin?
A: The module's internal system logic remains operational due to the >=500 VDC galvanic isolation boundary. The overcurrent condition remains isolated to that specific field loop, preventing the electrical spike from compromising the parallel operation of the remaining 31 digital output channels.
Q: Can this 1.36 kg digital output module be extracted from the FIO node while the ProSafe-RS safety loop is actively monitoring a live process?
A: No. Extracting a safety-critical output module under power will instantly interrupt the dry contact relay loops, dropping current to all 32 channels. This will cause downstream solenoids or actuators to de-energize immediately, triggering a process shutdown or safety interlock trip unless the field loops are bypassed at the marshalling panel first.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.