The Yokogawa AAM11 operates as a Current/Voltage Input Module designed for acquisition of DC voltage and current signals, with auxiliary voltage output capability and software‑defined input range settings.
Model: AAM11
Brand: Yokogawa
Origin: Japan
Weight: Not specified
Dimensions: Not specified
Operating Temp: Not specified
Power Consumption: ≤300 mA at 5.0 V DC
Input Signal: 0 to 10 V DC
Input Resistance: 1 MΩ (100 kΩ at power‑down)
Allowable Input Voltage/Current: -10 to 30 V DC
Transmitter Power Supply: 25.0 to 25.5 V DC (≤60 mA DC)
Auxiliary Voltage Output: 1 to 5 V DC; ≤1 Ω output resistance; ≥10 kΩ load resistance
Signal Grounding: Shared with system
Square Root Extraction: Available by specification
Accuracy Rating: Voltage input ±4 mV; Current input ±16 µA; Auxiliary voltage output ±12 mV
Effect of Ambient Change: 10 deg C variation → Voltage input ±4 mV and ±0.15 % of value; Current input ±32 µA; Auxiliary voltage output ±24 mV
Data Update Period: 50 ms
Signal Insulation: Input signals insulated between systems
Withstanding Voltage: 1500 V AC/min
Installation: I/O Module Nest
Wiring: M4 screw terminal connection
Input Signal Settings: Configurable via software
The AAM11 supports integration with 4-20 mA HART loop protocol, enabling deterministic current and voltage signal acquisition. Input signals are insulated between systems, with 1500 V AC/min withstand capability. Auxiliary voltage output is designed for stable reference supply, with shared grounding requiring strict adherence to system grounding practices.
Q: Can the AAM11 module be hot-swapped? A: Hot-swap capability is not specified. It is recommended to power down the I/O nest before replacement.
Q: How is square root extraction configured? A: Square root extraction is enabled through software specification, allowing direct processing of flow-related signals.
Q: What precautions are required for auxiliary voltage output wiring? A: Ensure load resistance ≥10 kΩ and maintain single-point grounding to prevent interference.
Install the module securely into the I/O Module Nest.
Connect wiring to terminal blocks using M4 screws with proper torque.
Maintain shield grounding at one point to avoid ground loops.
Separate signal wiring from high-voltage cabling to minimize interference.
Configure input signal ranges via software before commissioning.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.