Sale
| Color / Pattern |
|
| Power Source |
|
| Communication Protocols |
|
| Controller Design |
|
The Yokogawa AAI135-S00 acts as a reliable interface for capturing 4 to 20 mA analog signals within the CENTUM VP distributed control system. This 8-channel module provides high-speed data acquisition while maintaining individual channel isolation to safeguard the system from field-side electrical interference. We supply this unit as 100% Brand New and Original factory stock.
AAI135: Analog Input Module (4 to 20 mA, 8-channel).
-S: Standard hardware type.
0: Standard type with explosion protection.
0: Basic functional specification.
Channels: 8 isolated input channels.
Signal Range: 4 to 20 mA DC.
Power Draw: 360 mA at 5 V DC and 450 mA at 24 V DC.
Isolation: Individual channel-to-channel and system-to-field isolation.
Connectivity: Compatible with pressure clamp terminals, MIL connector cables, and KS1 dedicated cables.
Form Factor: Compact 10.7 cm x 13 cm x 3.3 cm footprint.
The AAI135-S00 solves the common industrial challenge of ground loops and signal noise by isolating every channel, ensuring that a fault on one loop does not jeopardize the entire I/O rack. Its straightforward "basic type" architecture allows for rapid replacement and commissioning without complex software mapping. The module's low power consumption profile reduces heat buildup in sealed control cabinets, while its compatibility with KS1 cables enables a clean, organized marshaling setup that simplifies long-term maintenance.
What is the difference between the -S00 and -S50 models?The -S00 designation includes standard explosion protection support, whereas the -S50 is the basic version without explosion protection. Always verify your site's hazardous area requirements before selection.
How does isolation benefit my control loop?Channel isolation prevents electrical noise from propagating between field devices. If one sensor shorts to ground, the other 7 channels on the AAI135-S00 continue to provide accurate data without interruption.
Can I use this module for 0-20 mA signals?This module is specifically calibrated for the standard 4 to 20 mA industrial range. Using it outside this range may result in signal errors or failure to meet accuracy specifications.
Is this a current-sourcing or current-sinking module?The AAI135-S00 is designed to receive 4-20 mA signals from field transmitters; the wiring configuration (2-wire vs. 4-wire) depends on your specific terminal board and jumper settings.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.