Sale
| Color / Pattern |
|
| Power Source |
|
| Controller Design |
|
The ICS Triplex T8431 is a Trusted Triple Modular Redundancy (TMR) analogue input module engineered for high‑integrity safety and control systems. Operating at 24 VDC, it provides fault‑tolerant signal acquisition across 40 analogue input channels, ensuring reliable measurement in safety‑critical environments.
Manufacturer: ICS Triplex
Product No.: T8431
System Supply Voltage Range: 20–32 VDC
Number of Inputs: 40 channels
User Defined Thresholds: 4 configurable thresholds
Input Current Range: 0–22 mA
Input Voltage Range: 0–6 VDC
Sample Update Time: 0.5 ms
Resolution: 3.9 µA (1/256 mA)
Safety Accuracy: ±1% of full scale
Calibration Accuracy: 0.03%
Calibration Interval: Recommended every 2 years
Circuit Type: Fault‑tolerant, fully triplicated with optional line monitoring
Fusing: None (external if required)
Intrinsic Safety: Requires external barrier
Sequence of Events:
Event resolution: 1 ms
Timestamp accuracy: ±0.5 ms
Field Common Isolation:
Sustained: ±250 VDC
Maximum withstand: ±2.5 kVDC
Channel Crosstalk: –40 to –60 dB
Power Consumption: 15–18 W
Self‑Test Interval: 2 minutes
Operating Temperature: –5 °C to +60 °C (23 °F to 140 °F)
Storage Temperature: –25 °C to +70 °C (–13 °F to 158 °F)
Temperature Change Rate: 0.5 °C/min
Operating Humidity: 10–95% RH, non‑condensing
Environmental Specifications: Refer to ICS Triplex Document 552517
Dimensions:
Height: 266 mm (10.5 in)
Width: 31 mm (1.2 in)
Depth: 303 mm (12 in)
Weight: 1.149 kg (2.5 lb)
Shipping Weight: 2 kg
Real Time Clock Resolution: 100 µs
The T8431 is ideal for oil & gas, petrochemical, power generation, and transportation industries, where precise analogue signal acquisition is required. It is commonly used for monitoring temperature, pressure, and flow transmitters in emergency shutdown (ESD), fire & gas detection, and turbine control systems.
Q: How many analogue inputs does the T8431 support? A: It provides 40 analogue input channels.
Q: What is the resolution of the module? A: 3.9 µA (1/256 mA), ensuring high‑precision measurement.
Q: How often should calibration be performed? A: A calibration check is recommended every 2 years.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.