The 140ACI03000 analogue input module is part of the Schneider Electric Modicon Quantum automation platform. It provides high-precision differential signal acquisition with robust isolation, fast update times, and built-in fault detection, making it suitable for demanding industrial automation environments.
Product Range: Modicon Quantum automation platform
Type: Analogue input module
Filter Type: Single-pole low-pass, -3 dB at 15 Hz ±20%
Number of Inputs: 8 differential channels
Addressing Requirement: 9 input words
Resolution: 12-bit
Measuring Ranges:
1–5 V DC
4–20 mA DC
Absolute Maximum Input:
50 V DC
25 mA
Input Impedance:
250 Ω (current) ±0.01%
20 MΩ (voltage)
Accuracy:
±0.05% of full scale typical
±0.1% of full scale maximum
Linearity Error: ±0.04%
Temperature Drift:
±0.0025% of full scale/°C typical
≤ ±0.005% of full scale/°C maximum
Common Mode Rejection: > -72 dB at 60 Hz
Isolation:
Channel-to-bus: 1000 V DC, 3000 V DC for 60 s
Channel-to-channel: 30 V DC
Update Time: 5 ms
Fault Detection:
Broken wire (4–20 mA)
Undervoltage (1–5 V)
Indicators:
1 green LED for bus communication
1 red LED for external fault
8 green LEDs for channel active
8 red LEDs for channel fault
Bus Current Requirement: 240 mA
Power Dissipation: 2 W
Format: Standard Quantum module
Weight: 0.3 kg (0.7 lb US)
Operating Temperature: 0–60 °C (32–140 °F)
Storage Temperature: -40–85 °C (-40–185 °F)
Relative Humidity: Up to 95% non-condensing
Altitude: ≤ 5000 m (16404 ft)
Electrostatic Discharge Resistance: 4 kV contact, 8 kV air (IEC 801-2)
Electromagnetic Field Resistance: 9.1 V/m (IEC 801-3, 80–1000 MHz)
CE Marking
UL 508
CSA C22.2 No.142
FM Class 1 Division 2
cUL
This analogue input module is ideal for monitoring industrial process variables such as temperature, pressure, and flow. Its high resolution and fast update time make it suitable for precision control in manufacturing, utilities, and energy systems.
Q: What types of signals can this module measure? A: It supports both voltage (1–5 V) and current (4–20 mA) signals.
Q: How does the module detect faults? A: It identifies broken wires in 4–20 mA loops and undervoltage conditions in 1–5 V inputs.
Q: What is the resolution of the analogue inputs? A: The module provides 12-bit resolution for accurate signal acquisition.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.