Sale
The Honeywell RM7895A1014, also cataloged as the RM7895A1014 Burner Control Unit, operates as a dedicated hardware component for primary flame safeguard execution and automatic burner sequencing within industrial combustion networks. Operating on a 120 VAC (50/60 Hz) power supply, the microprocessor-based relay module processes intermittent pilot ignition, intermittent main flame establishing periods, selectable interlocks, and purge timing dictated by an ST7800A plug-in purge timer card.
| Parameter | Specification |
|---|---|
| Model | RM7895A1014 |
| Brand | Honeywell |
| Origin | USA |
| Weight | 0.9 kg (Module); 2.9 kg (Shipping Weight) |
| Dimensions | 127 mm W x 127 mm H x 133 mm D (Q7800A) / 155 mm D (Q7800B) |
| Operating Temp | -40 to +60 deg C |
| Storage Temp | -40 to +60 deg C |
| Power Consumption | Standard 120 VAC Base Load |
| Input Voltage | 120 VAC (+10, -15%) |
| Frequency | 50/60 Hz (+/- 10%) |
| Pilot Flame Period | 4 sec or 10 sec |
| Main Flame Period | Intermittent |
| Pilot Type | Intermittent |
| PrePurge | Determined by ST7800A Plug-in Purge Timer Card |
| Delayed Main Valve | No |
| Vibration Resistance | 0.5 G environment |
| Required Subbase | Q7800A or Q7800B Universal Wiring Subbase |
The RM7895A1014 utilizes internal signal filtering and channel-to-channel isolation principles to shield sensitive microampere flame sensor amplifier circuits (R7847, R7848, R7849, R7851, R7852, R7861, or R7886) from high-voltage AC ignition interference and line power fluctuations. The solid-state control architecture decouples low-voltage diagnostic loops and purge timing circuits from the main 120 VAC switching relays and external field wiring terminals. This strict isolation topology prevents ground-loop current shifts and eliminates inductive cross-talk, maintaining deterministic sequence control, continuous flame validation, and rapid safety lockout execution.
Q: How is the pre-purge timing duration established on the RM7895A1014 relay module?
A: Pre-purge duration is strictly determined by inserting a compatible ST7800A Plug-in Purge Timer Card into the front-facing header interface of the module prior to energizing the unit.
Q: What mandatory hardware components must be combined with the RM7895A1014 for operation?
A: The module requires a Q7800A or Q7800B Universal Wiring Subbase, an ST7800A Plug-in Purge Timer Card, and a compatible 7800 Series Flame Signal Amplifier (such as R7847, R7848, R7849, R7851, R7852, R7861, or R7886).

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.