Sale
Configured for high-availability analog output processing in Honeywell Experion PKS and TPS networks, the HONEYWELL 8U-TAOXB1 (8U-TAOXB1 Analog Output Module) provides direct physical/electrical execution. Operating on standard IOPS unit power supply, this IOTA series module manages software-configurable 4-20 mA or 0-10 VDC output loops, delivering high-precision 16-bit D/A conversion with continuous diagnostic coverage across an operating temperature range of -20 to +70 deg C.
| Parameter | Specification |
|---|---|
| Model | 8U-TAOXB1 |
| Brand | Honeywell |
| Origin | USA |
| Weight | Standard IOTA Chassis Weight (Approx. 0.65 kg) |
| Dimensions | Standard Series 8 IOTA Assembly Form Factor |
| Operating Temp | -20 to +70 deg C |
| Power Consumption | Powered via IOPS (I/O Power Supply) unit |
| Output Type | Redundant Analog Output (Single-Ended) |
| Signal Range | 4-20 mA or 0-10 V DC (Software-configurable per channel) |
| Load Drive Capability | Up to 750 ohm at 20 mA |
| Output Accuracy | +/- 0.1% of full scale |
| Resolution | 16-bit D/A conversion |
| Update Rate | <= 100 ms per channel |
| Redundancy Switchover Time | < 500 ms |
| Isolation | 500 VDC between field and system circuits |
| Backplane Interface | IOI/HIGHWAY at 1.2 Mbit/s or 4 Mbit/s |
The 8U-TAOXB1 module incorporates 500 VDC galvanic isolation barriers to isolate internal backplane logic processing from field-side electrical transients and earth ground potential shifts. Each 16-bit D/A conversion driver supports 4-20 mA current loop transmission across field loads reaching 750 ohm without degrading signal resolution or thermal dissipation boundaries. High-speed backplane integration via the IOI/HIGHWAY bus ensures continuous diagnostic polling and redundant module state execution, achieving automatic failover in under 500 ms to preserve continuous closed-loop control integrity.
Q: Does the 8U-TAOXB1 module support hot-swapping during active system operation?
A: Yes. The 8U-TAOXB1 module features a hot-swappable IOTA architecture that allows live insertion and removal of redundant hardware modules without dropping active output channels or interrupting system power.
Q: How are individual channel signal output ranges configured?
A: Output ranges (4-20 mA current loops or 0-10 VDC voltage outputs) are configured on a per-channel basis strictly through Experion system software parameters, eliminating the need for hardware jumpers.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.