Sale
| Color / Pattern |
|
| Power Source |
|
| Communication Protocols |
|
| Controller Design |
|
The Honeywell 2MLF‑AD8A, also cataloged as the 2MLF‑AD8A analog input module, serves as an 8‑channel current/voltage acquisition unit used to execute multi‑format analog signal conversion across HC900/ControlEdge measurement platforms.
| Parameter | Specification |
|---|---|
| Model | 2MLF‑AD8A |
| Brand | Honeywell |
| Origin | HC900 / ControlEdge I/O Platform |
| Weight | 140 g (shipping weight 2 kg) |
| Dimensions | Not specified |
| Operating Temp | Not specified |
| Power Consumption | Not specified |
| Product Type | 8‑Channel Analog Input Module |
| Channels | 8 channels per module |
| Data Format | Signed −8000 to 8000; Precise 4000–20000 / 0–20000; Percentile 0–10000 |
| Resolution | 14‑bit binary (data: 14 bits) |
| Max Conversion Speed | 250 µs per channel |
| Absolute Max Input | ±15 V, ±30 mA |
| Isolation Method | Photo‑coupler isolation between input terminal and PLC power (no channel‑to‑channel isolation) |
| Terminal Block | 18‑point terminal block |
| I/O Addressing | Fixed 64 points; variable 16 points |
Although the 2MLF‑AD8A is a voltage/current measurement module rather than a loop‑powered transmitter interface, its conversion architecture aligns with Honeywell’s process‑instrumentation conventions. When installed alongside HC900 analog modules, the backplane maintains deterministic timing for 4‑20 mA HART loop protocol devices. The module uses photo‑coupler isolation between input terminals and PLC power, while HC900 I/O modules preserve channel‑to‑channel isolation for adjacent analog modules to prevent cross‑loop interference.
Q: Can the 2MLF‑AD8A be hot‑swapped during operation? A: No. The module must be inserted or removed only when the controller rack is de‑energized.
Q: Does the 250 µs/channel conversion speed affect controller scan timing? A: Conversion speed determines how quickly each analog channel updates. Overall scan timing depends on the controller’s configured I/O strategy.
Q: Can each channel use a different data format? A: Yes. Each channel’s digital output format can be individually configured through user logic or via the SoftMaster I/O parameter interface.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.