Sale
| Color / Pattern |
|
| Power Source |
|
| Communication Protocols |
|
| Controller Design |
|
Serves as the primary GE WESDAC D20C I/O Module utilized to execute digital and analog field signal processing across GE D20 RTU automation platforms.
The D20C system consists of a two-part hardware architecture comprising a main processing module paired with a dedicated termination assembly:
| Parameter | Specification |
|---|---|
| Model | WESDAC D20C |
| Brand | GE |
| Origin | USA |
| Weight | Approx. 1.20 kg |
| Dimensions | Standard D20 Subrack Slot Card |
| Operating Temp | -20 to +70 deg C |
| Power Consumption | Subrack Backplane / D.20 Link Bus Powered |
| Processor | 8-bit Freescale 68HC11 MPU @ 2 MHz |
| On-Board Memory | 24 KB EPROM, 32 KB Static RAM, 512 bytes EEPROM |
| Digital Inputs | 16 Channels |
| Control Outputs | 8 Momentary or Dual-Function Relay Outputs |
| Optional Daughterboard 1 | 16 Analog Inputs (Bipolar, Differential, 14-bit plus sign resolution) |
| Optional Daughterboard 2 | 8 Analog Inputs and 8 Analog Outputs (Unipolar/Bipolar, 12-bit plus sign resolution) |
| Analog Input Conversion | 275 ms (16 channels @ 60 Hz), 328 ms (16 channels @ 50 Hz) |
| Serial Interfaces | 2x DB9 D.20 Link Daisy-Chain Ports, 1x DB9 WESMAINT D20 Maintenance Port |
The WESDAC D20C employs dual DB9 serial interface connections to execute high-speed D.20 Link communications across distributed controller racks. Internal processing offloads loop scanning from the central D20 main processor using an on-board 68HC11 microcontroller running at 2 MHz clock speed. The module processes 16-channel analog updates within 275 ms (at 60 Hz filtering) and executes local I/O density scaling with 95 dB common-mode noise rejection, maintaining deterministic data delivery over internal bus topographies.
Q: How is local maintenance performed on the WESDAC D20C without interrupting backplane serial traffic?
A: The card features a dedicated DB9 WESMAINT port on the front panel, allowing direct ASCII terminal access for diagnostics while maintaining active polling on the secondary D.20 Link daisy-chain ports.
Q: What is the purpose of the Local/Remote switch located on the front panel of the module?
A: The Local/Remote toggle switch isolates relay coil power output circuits during maintenance, preventing accidental field tripping while providing module status feedback to the host controller.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.