Configured for precise electrical parameter monitoring in AC distribution systems, the GE PQMII-C-A (PQMII Power Quality Meter) provides direct physical/electrical execution.
The PQMII-C-A hardware model string defines specific factory options and functional card configurations:
| Parameter | Specification |
|---|---|
| Model | PQMII-C-A |
| Brand | GE |
| Origin | USA |
| Weight | Approx. 1.20 kg |
| Dimensions | Standard 1/4 DIN Panel Cutout (192 x 192 mm) |
| Operating Temp | -20 to +70 deg C |
| Power Consumption | Control Power Input Rails |
| Current Conversion | True RMS, 64 samples/cycle |
| CT Secondary Input | 1 A and 5 A secondary |
| CT Burden & Overload | 0.2 VA burden; 20x CT for 1 sec, 100x CT for 0.2 sec |
| Current Accuracy | ±0.2% of full scale (at <1.20x CT) |
| Voltage Input Range | 40 to 600 VAC (VT Ratio 1:1 to 3500:1) |
| Voltage Accuracy | ±0.2% of full scale |
| Harmonic Frequency | Up to 32nd harmonic analysis |
| Switch Inputs | Dry contacts (24 VDC @ 2 mA pulsed output, 1000 ohm max ON resistance) |
The PQMII-C-A processes True RMS voltage and current waveforms at 64 samples per cycle, executing internal DSP calculation routines up to the 32nd harmonic. Channel-to-channel signal isolation across CT and VT inputs prevents ground loops, while high-velocity internal processing scales I/O density by mapping real-time metering values into 24 VDC pulsed switch input detection loops without cycle measurement degradation.
Q: What are the current transformer (CT) overload thresholds supported by the PQMII-C-A?
A: The CT input circuitry withstands temporary current overloads up to 20 times nominal CT rating for 1 second, and up to 100 times nominal CT rating for 0.2 seconds.
Q: How does the module handle switch input signal sensing?
A: The switch inputs detect dry contact states using an internally generated 24 VDC at 2 mA pulsed output, requiring a maximum ON resistance of 1000 ohms and a minimum pulse duration of 100 ms.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.