Configured for high-resolution temperature monitoring in Mark VIe turbine control networks, the GE IS220PTCCH2BB (IS220PTCCH2BB Thermocouple Input Pack) provides direct physical/electrical execution. The specialized hardware serves as a 12-channel digitizing interface that conditions low-voltage analog millivolt profiles from distinct thermocouple sensors into synchronous digital variables across dual Ethernet backplane links.
| Parameter | Specification |
|---|---|
| Model | IS220PTCCH2BB (Associated sub-assembly: IS230SNTCH4A) |
| Brand | General Electric (GE) |
| Origin | United States (USA) |
| Weight | 1.5 kg |
| Dimensions | 241 mm x 194 mm x 152 mm |
| Operating Temp | -25 to +60 deg C (Continuous ambient operational bounds) |
| Humidity Range | 5 to 95 % RH non-condensing tracking limits |
| Power Consumption | Sourced via dual distribution rails; operates at 24 VDC or 125 VDC nominal |
| Input Channels | 12 non-interfering thermocouple input tracks |
| Sensor Compatibility | Thermocouple Types E, J, K, S, T, B, N, R |
| A/D Resolution | 16-bit analog-to-digital converter architecture |
| Control Redundancy | Simplex, Dual, and Triple Modular Redundant (TMR) configurations |
| Communication Ports | Dual redundant Ethernet interfaces |
| Safety Compliance | SIL 2 / SIL 3 certified metrics |
Q: How does the module execute reference tracking when deployed in a TMR architecture?
A: In a Triple Modular Redundant (TMR) deployment, three identical PTCC packs interface with the same thermocouple field signals. Each pack evaluates the 16-bit digital value independently and streams it over isolated Ethernet paths to the primary controllers, where a 2oo3 (two-out-of-three) hardware voting loop checks channel validity and isolates transient sensor failures.
Q: Can the thermocouple input type be modified per channel without reloading the core I/O pack firmware?
A: Yes. The input channel configuration matrix is defined inside the controller software interface. Individual parameters for sensor types E, J, K, S, T, B, N, or R can be software-selected on a per-channel basis, enabling real-time scaling adaptation without flashing the core hardware bootloader code.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.