The GE IS220PHRAH1B, also cataloged as the IS220PHRAH1B HART Enabled Analog I/O Module, operates as a dedicated hardware component for high-precision analog signal processing and bidirectional HART protocol routing within Mark VIe control systems. This localized processor module plugs directly into an analog terminal board, digitizing 10 analog inputs via internal converter arrays while generating 2 current loop outputs to govern field-mounted actuators.
| Parameter | Specification |
|---|---|
| Model | IS220PHRAH1B / IS230SNHRH2A |
| Brand | GE (General Electric) |
| Origin | United States (USA) |
| Dimensions | 3.25 in x 1.65 in x 4.78 in |
| Operating Temp | Standard Mark VIe panel environmental limits (0 to 65 deg C typical) |
| Product Type | HART Enabled Analog I/O Module |
| Channel Capacity | 12 total channels (10 analog inputs / 2 current loop outputs) |
| Input Resolution | 16-bit analog-to-digital (A/D) converter resolution |
| Output Resolution | 14-bit digital-to-analog (D/A) converter resolution |
| Loop Scan Time | 5 ms normal scan interval velocity |
| Maximum Output Load | 800 ohms maximum load resistance for 4-20 mA output loops |
| Network Connectors | Dual RJ45 Ethernet interfaces for redundant network linking |
| Power Configuration | 3-pin dedicated power input connector |
| Interface Port | DC-62 pin connector for terminal board mating |
| Circuit Technology | Surface-mount technology (SMT) component layout |
| Diagnostics Interface | Onboard status indicator LEDs and local infrared (IR) serial port |
Q: How does the module handle communication redundancy over the dual RJ45 ports?
A: The IS220PHRAH1B incorporates two completely independent RJ45 Ethernet controllers that run parallel connections to separate network switches. Process values, HART diagnostic fields, and system commands are broadcast concurrently across both links, enabling a bump-free switchover if one line experiences a packet loss or physical rupture.
Q: What function does the integrated infrared (IR) port perform during field maintenance?
A: The infrared transceiver establishes a localized serial link to read real-time error logs and push configuration profiles without requiring physical plug connections. This optical link keeps the module sealed against ambient contaminants while allowing technicians to query internal 16-bit register arrays locally.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.