The GE IS230SNRLH2A, also cataloged as the IS200TRLYH2A Discrete Output Relay Module, operates as a dedicated hardware component for contact switching and field device actuation within Mark VIe and Mark VIeS turbine control systems. This DIN-rail mounted assembly serves as a direct physical and electrical execution interface, deploying 12 Form-C mechanical relays to switch heavy field-side elements including solenoids, external alarms, and drive contactors.
| Parameter | Specification |
|---|---|
| Model | IS230SNRLH2A / IS20OSNRLH2A |
| Brand | GE (General Electric) |
| Origin | United States |
| Weight | 1.14 kg net hardware mass profile |
| Dimensions | 15.9 cm x 17.8 cm x 6.8 cm |
| Operating Temp | -40 to +70 deg C extended environmental envelope |
| Product Type | Discrete Output Relay Module |
| Output Capacity | 12 Form-C relays (Changeover architecture) |
| Relay Load Rating (DC) | 24 VDC @ 5 A; 48 VDC @ 1.2 A; 125 VDC @ 0.6 A continuous |
| Operating Mode | Simplex configuration (Non-redundant signal deployment) |
| Terminal Interface | Euro-style box terminal blocks |
| Connector Interface | D-shell female connection matrix |
| Circuit Technology | Surface-mount technology (SMT) layout design |
| Environmental Protection | Factory-applied conformal board coating choice |
| Hazardous Certifications | UL E2067685, Class I Division 2, Groups A, B, C, D |
Q: Can this simplex relay module be wired to support a Triple Modular Redundant (TMR) voting structure?
A: No. The internal electrical copper pathways, trace distribution, and signal paths of the IS230SNRLH2A are explicitly engineered to run in simplex mode only. It lacks the redundant terminal headers and shared trace splits needed to distribute coil loads across three independent processing channels.
Q: How does the choice of external operating voltage affect the continuous contact current thresholds?
A: The contact ratings are bounded by the inductive arcing profiles of the chosen voltage. The mechanical contacts safely commute up to 5 A under a low-voltage 24 VDC threshold, but the current limit scales down sharply to 1.2 A at 48 VDC, and drops to a maximum of 0.6 A when handling heavy 125 VDC station battery lines.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.