The General Electric IS200JPDEG1AAA, also cataloged as the IS200JPDE DC Battery Power Distribution Board, operates as a dedicated hardware component for DC power distribution and fault monitoring within Mark VIe PDM (Power Distribution Modules) platforms.
| Parameter | Specification |
|---|---|
| Model | IS200JPDEG1AAA |
| Brand | General Electric |
| Origin | United States |
| Weight | Standard industrial weight for Mark VIe JPDE boards |
| Dimensions | 17.08 cm wide x 16.51 cm high |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | Power distributed from external battery/supply, supports 24 VDC or 48 VDC modes |
| Number of Channels | 24 |
| Voltage Range | 18 - 32 VDC |
| Input Isolation | 1,500 V |
| AC Voltage Rejection | 60 V RMS |
| Technology | Surface mount |
| Mounting | DIN-rail mounting |
The IS200JPDEG1AAA routes DC power paths across a maximum of 24 channels while sustaining backplane bus communication velocity and diagnostics via P1/P2 feedback connectors. These linkages tie into the JPDB, JPDF, JPDS, and JPDM modules, transmitting core electrical metrics directly to the PPDA I/O pack. The architecture incorporates dual 50-pin diagnostic connectors positioned on both the upper and lower boundaries of the board, allowing structural data acquisition and real-time power bus monitoring. This dual-connector loop facilitates deterministic tracking of the floating DC bus configuration, which is mechanically centered on earth ground using a discrete resistor network.
Q: How does the IS200JPDEG1AAA manage system ground fault detection?
A: The board establishes a floating DC bus centered on earth ground via a network of onboard resistors. Voltage feedback is routed continuously through the PPDA I/O pack to calculate ground fault deviations.
Q: What are the primary isolation and rejection boundaries for this module?
A: The board provides galvanic input isolation rated at 1,500 V and features an AC voltage rejection threshold of 60 V RMS to prevent noise propagation across the DC distribution lines.
Q: Does this board provide input power for bulk 500W power supplies?
A: No, the current passing capabilities of this board's conventional construction limit its output paths; it does not supply power to bulk 500W (24 V input/28 V output) supplies that drive I/O pack control power.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.