Configured for high-density discrete signal processing, electronic load modulation, and smart instrumentation tracking, the GE IC660BBD024 (IC660BBD024 Source I/O Block) provides direct physical/electrical execution. The distributed subsystem interfaces 2-wire and 3-wire DC sensors natively at the hardware tier to route binary channel data across localized token-passing serial fieldbus networks.
| Parameter | Specification |
|---|---|
| Model | IC660BBD024 |
| Brand | General Electric (GE) |
| Series | Genius I/O / Series 90-30 and 90-70 Subsystems |
| Origin | United States of America (USA) |
| Weight | 4 lbs (1.81 kg) |
| Dimensions | 22.44 cm x 9.05 cm x 11.23 cm |
| Nominal Operating Voltage | 12/24 VDC single-source line |
| Operating Voltage Range | 10 to 30 VDC continuous input envelope |
| Required Internal DC Power | 150 mA typical / 300 mA maximum continuous load |
| Power Supply Dropout Tolerance | 4 ms at 12 VDC / 20 ms at 24 VDC |
| Channel Density | 32 discrete points (individually configurable) |
| Circuit Configuration | Input, output, or output with feedback modes (Sourcing logic) |
| Steady-State Output Current | 0.5 A maximum per circuit |
| Maximum Output Inrush Current | 4 A up to 10 ms (maximum frequency once every 0.5 sec) |
| Aggregate Block Output Current | 16 A maximum simultaneous threshold |
| Input Impedance | 3.3 k Ohms typical |
| Input Processing Latency | 1.4 ms base plus programmable filter delay configuration |
| Selectable Input Filter Times | 1, 2, 3, 4, 5, 10, 20, 30, 40, 50, 60, 70, 80, 90, or 100 ms |
| Block-to-Block Isolation | 850 V galvanic isolation barrier |
| Operating Temperature Range | 0 to +60 deg C (+32 to +140 deg F) |
| Relative Humidity Limits | 5% to 95% RH, non-condensing |
| Product Type | Distributed I/O Modules |
Q: What programmatic or electrical faults manifest if an output wiring error creates a shorted electrical load?
A: The module's internal self-protecting solid-state switches detect the overcurrent state and latch off the faulted channel driver instantly. The block concurrently sets a "Switch Fault" error flag, generates an explicit diagnostic data package across the fieldbus link, and turns off the corresponding individual logic-side LED.
Q: Can the internal electronics module assembly be replaced while the field wire terminations remain connected?
A: Yes, the mechanical footprint consists of a separate terminal base (IC660TBD024) and a plug-in electronics module (IC660EBD024). This structural split allows online extraction and insertion of the electronic component board without disturbing field terminations or requiring system re-parameterization.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.