The GE Fanuc IC660BBA026, also cataloged as the IC660BBA026 Analog Input Module, operates as a dedicated hardware component for multi-channel analog signal processing, current-loop telemetry interception, and distributed register mapping within Genius network architectures. The rackless field block utilizes internal voltage-to-frequency conversion circuits natively at the hardware tier to digitize 4-20 mA inputs without requiring a central chassis backplane.
| Parameter | Specification |
|---|---|
| Model | IC660BBA026 |
| Brand | GE Fanuc / Emerson |
| Series | Genius I/O System |
| Origin | United States of America (USA) |
| Product Weight | 2.00 lbs (0.91 kg) |
| Dimensions | 8.83 x 3.34 x 3.91 inches (22.44 x 8.48 x 9.93 cm) |
| Input Channel Density | 6 analog current-source inputs (Single group of 6) |
| Analog Input Signal Range | 4-20 mA current loop processing |
| Signal Conversion Accuracy | 0.1% of full-scale reading |
| Input Scaling Resolution | 1 microamp (1 microamp / 6 microamp variant scaling) |
| External Supply Input Range | 18 to 56 VDC continuous current loops (24 V loop rated at 25 mA) |
| Primary Block Power Options | 115 VAC / 125 VDC nominal line feeds |
| User-Selectable Conversion Time | 16.6 ms to 400 ms software-configured intervals |
| Typical Thermal Drift | 70 PPM per deg C |
| Maximum Heat Dissipation | 12 W continuous load |
| Isolation Protection Limits | 1500 V block-to-block / 1500 V RMS group-to-group barrier |
| Visual System Diagnostics | Faceplate LEDs (Unit OK, I/O Enabled) |
| Product Type | Analog Input Modules |
Q: What precise diagnostic actions manifest if an analog field line drops below 2 mA?
A: A signal drop below the 2 mA threshold triggers the module's embedded open-wire and underrange diagnostic logic. The block instantly flags a low-alarm fault word over the Genius network link, passes an error state bit to the host controller register, and surfaces the condition on the configuration terminal.
Q: Can this rackless module be calibrated in the field using a handheld monitor device?
A: No, the IC660BBA026 internal signal conditioning and conversion components are factory-calibrated and do not require manual adjustment. A Phase B Hand-Held Monitor (HHM) is utilized exclusively to manage software parameters, establish alarm limits, adjust conversion times, and clear active error logs.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.