Configured for high-performance processing in AC2000, DC2000, and EX2000 excitation drive systems, the GE DS200SDCCG1AHD (DS200SDCC Drive Control Card) provides direct physical/electrical execution.
The alphanumeric characters of the DS200SDCCG1AHD functional product number decode into specific hardware, coating, and revision identifiers:
| Segment | Code | Description |
|---|---|---|
| Series Tag | DS200 | Standard Mark V assembly, domestic US manufacturing location |
| Board Acronym | SDCC | Drive Control Card functional product designation |
| Coating Style | G | Normal protective board coating |
| Series Group | 1 | Group 1 Mark V Series product grouping (AC/DC/EX2000 applications) |
| Revision 1 | A | A-rated primary functional board revision |
| Revision 2 | H | H-rated secondary functional board revision |
| Artwork Rev | D | D-rated mechanical artwork layout configuration |
| Parameter | Specification |
|---|---|
| Model | DS200SDCCG1AHD |
| Brand | General Electric (GE) |
| Origin | USA |
| Weight | 1.45 kg |
| Dimensions | 280 mm x 195 mm x 30 mm |
| Operating Temp | 0 to 55 deg C |
| Core Processors | 3x onboard microprocessors |
| Onboard RAM | Multi-port shared RAM with simultaneous microprocessor access |
| Power Inputs | +5 VDC, +/- 15 VDC, and +24 VDC via 2PL card connector |
| Connectivity | Supports LAN communications auxiliary cards via dedicated headers |
Operating as the primary computational engine for turbine drives, the SDCC architecture distributes complex math and signaling workloads across three specialized onboard processors.
Q: What is the primary function of the 2PL card connector on the DS200SDCCG1AHD?
A: The 2PL connector serves as the main DC power interface. It imports regulated +5 VDC, +/- 15 VDC, and +24 VDC power rails directly from the Power Supply / Interface Board to power the onboard logic and signal scaling circuitry.
Q: How is the drive control card configured or tuned during commissioning?
A: Configuration requires a serial connection from a local laptop to the serial port found on the optional LAN communications auxiliary card. Operators must utilize dedicated GE configuration software to download, edit, and upload the master drive configuration files.
Q: Can the same configuration file be uploaded to multiple SDCC boards?
A: Yes. If multiple drives across the system share identical operating parameters, the edited configuration file can be uploaded sequentially to each board to ensure software standardization and reduce commissioning time.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.