Sale
| Color / Pattern |
|
| Power Source |
|
| Communication Protocols |
|
| Controller Design |
|
The GE Multilin 750-P5-G1-S1-HI-A20-R, also cataloged as the 750-P5-G1-S1-HI-A20-R Feeder Management Relay, serves as the primary 750 Feeder Management Relay utilized to execute comprehensive monitoring, circuit breaker control, and automated fault isolation across medium-to-large utility and industrial power distribution networks.
The 750 series utilizes explicit alphanumeric codes within its ordering matrix to define the integrated hardware options and functionality block baseline:
| Parameter | Specification |
|---|---|
| Model | 750-P5-G1-S1-HI-A20-R |
| Brand | GE Multilin (General Electric) |
| Origin | Canada / USA |
| Weight | Standard Multilin 750 series switchgear drawout case baseline applies |
| Dimensions | approx. 18 cm W x 21.5 cm H x 16.5 cm L (7.09" x 8.46" x 6.50") |
| Operating Temp | Standard industrial protection relay environmental parameters apply |
| Operating Humidity | Up to 90% non-condensing relative humidity parameters |
| Power Consumption | Control Power range: 88-300 VDC / 70-265 VAC at 48-62 Hz frequency bounds |
| Product Type | Feeder Management Relays |
| Current Inputs | 5 A phase current inputs / 1 A zero sequence and sensitive ground inputs |
| Analog Outputs | Eight independent 4 to 20 mA analog output loops |
| Discrete Logic Inputs | 20 total logic inputs (including 14 hardware rear contact inputs; wet/dry) |
| Output Relays | 8 electromechanical output relays (5 general purpose, 3 dedicated) |
| Overvoltage Pickup | 0 to 1.25 x VT scaling adjustable in steps of 0.01 |
| Communications | Serial copper bus supporting 300 to 19200 baud transmission rates |
| Pollution Degree | II standard industrial compliance rating |
Q: What specific assignments are pre-mapped to the three dedicated electromechanical output relays?
A: The three dedicated channels are hardwired for safety-critical operations: Trip Relay 1 executes rapid circuit breaker opening, Close Relay 2 manages breaker closure sequence timing, and the Self-Test Warning relay handles internal diagnostic fault signaling. The remaining five output contacts are fully user-programmable for auxiliary alerting or custom interlock logic.
Q: How do the rear-mounted logic contact inputs handle mixed field excitation voltages?
A: The 14 rear contact inputs are designed with high-dielectric optical isolation blocks that accept both dry (voltage-free contact closure) and wet (externally energized) signaling configurations. This dual-mode layout allows seamless integration with legacy control switches and modern digital breaker status contacts across the switchgear lineup.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.