Sale
| Color / Pattern |
|
| Power Source |
|
| Communication Protocols |
|
| Controller Design |
|
Configured for management, protection, and control of low and medium voltage motors in industrial electrical networks, the GE Multilin 339-E-P1-G1-H-E-S-N-P-3E-D-N (339-E-P1-G1-H-E-S-N-P-3E-D-N Motor Protection System) provides direct physical/electrical execution.
| Model Suffix | Core Function Architecture | Architectural Application |
|---|---|---|
| 339-E-P1-G1-H-E-S-N-P-3E-D-N | Comprehensive Motor Protection Relay with 1A Inputs | Low and Medium Voltage Motor Control Centers |
| 339-E... | Base Variant Family | GE Multilin 339 Series Protection Platforms |
| Parameter | Specification |
|---|---|
| Model | 339-E-P1-G1-H-E-S-N-P-3E-D-N |
| Brand | GE Multilin |
| Origin | Canada |
| Weight | 2.5 kg |
| Dimensions | 201.4 mm x 168.1 mm x 244.4 mm |
| Operating Temp | -20 deg C to +60 deg C |
| Power Consumption | 18.0 W nominal |
| Power Supply | 110-250 VDC / 110-230 VAC |
| Current Inputs | 3-Phase 1A, Ground 1A |
| Outputs | 2 Form A, 5 Form C |
The 339-E-P1-G1-H-E-S-N-P-3E-D-N relay integrates advanced communication processors to manage high-speed Ethernet, IEC 60870-5-104, and IEC 61850 protocol exchanges across substation automation architectures. It handles multi-channel voltage protections and custom FlexCurve thermal overload algorithms while maintaining precise timing accuracy. Furthermore, internal firmware flash compatibility enables secure software upgrades and parameter configuration over digital communication links without requiring physical board replacements.
Q: What power supply range does the 339-E-P1-G1-H-E-S-N-P-3E-D-N relay require for operation?
A: The unit operates on a high-voltage auxiliary power supply ranging from 110-250 VDC or 110-230 VAC.
Q: Does this specific model configuration include a harsh environment conformal coating?
A: No, this variant utilizes a standard drawout case design without the optional conformal coating, maintaining an IP40 rating on the front panel and IP10 on the rear.
Ensure that auxiliary control power and main motor circuit breakers are completely de-energized and locked out prior to mounting or wiring the 339-E-P1-G1-H-E-S-N-P-3E-D-N relay. Connect current transformer (CT) secondary leads securely to the 1A terminals, ensuring proper grounding to prevent dangerous open-circuit high voltages. Route all communication and control wiring through dedicated metal conduits, keeping signal cables separated from high-voltage power lines to minimize electromagnetic interference.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.