Sale
The Allen-Bradley 1769sc-IF4IH, also cataloged as the 1769sc-IF4IH Analog+ HART Input Module, operates as a dedicated hardware component for multi-channel HART instrument signal acquisition and backplane data conversion within CompactLogix / MicroLogix 1500 platforms.
| Parameter | Specification |
|---|---|
| Model | 1769sc-IF4IH |
| Brand | Allen-Bradley |
| Origin | USA |
| Weight | 0.56 lbs (0.26 kg) |
| Dimensions | Standard 1769 Compact I/O Single-Slot Width |
| Operating Temp | 0 to 60 deg C |
| Power Consumption | Standard 1769 Backplane Bus Powered |
| Product Line | CompactLogix |
| Product Type | Analog+ HART Input Module |
| Channels | 4 isolated input channels |
| Voltage Inputs | 0-5 V, 1-5 V, 0-10 V, +/-10 V |
| Current Inputs | 0-20 mA, 4-20 mA |
| Resolution | 16-bits |
| HART Variables | PV, SV, TV, FV |
| Accuracy | +/-0.2% of range voltage, +/-0.35% of range current |
| Filter Frequencies | 28.5 Hz, 50 Hz, 60 Hz, 300 Hz, 360 Hz |
| Update Times | 18 to 488 ms (all channels), 6 s (HART data) |
| Data Formats | Engineering units, Scaled-for-PID, Percent of full-scale, Raw/proportional |
| Certifications | UL/cUL Listed ANSI ISA 12.12.01 (Class I, Div 2, Groups ABCD), CE |
The module manages backplane bus communication velocity and real-time analog data translation across 1769 Compact I/O buses. Channel-to-channel signal integrity is maintained through selective Digital-to-Analog conversion paths operating at 16-bit resolution. Integrated firmware flash compatibility enables simultaneous pass-through of 4-20 mA HART loop protocol dynamic variables (PV, SV, TV, FV) directly into the controller image table without degrading backplane scanning deterministic performance.
Q: How does the 1769sc-IF4IH module handle simultaneous analog sampling and HART communication?
A: The internal analog-to-digital converter processes 4-20 mA analog signals at channel update times between 18 and 488 ms, while HART FSK data is scanned asynchronously across a 6-second update cycle per channel.
Q: Is external field power required for 4-20 mA loop operation on the 1769sc-IF4IH?
A: Field power depends on transmitter wiring configuration; active 4-wire transmitters supply loop voltage directly, whereas 2-wire loop-powered transmitters require an external 24 VDC loop power supply in series with the input terminals.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.