Sale
| Color / Pattern |
|
| Power Source |
|
| Controller Design |
|
The Yokogawa AAM11B functions as a Current/Voltage Input Module designed for acquisition of 0-20 mA DC signals, with transmitter power supply capability, auxiliary voltage output, and software‑defined input range settings.
Model: AAM11B
Brand: Yokogawa
Origin: Japan
Weight: Not specified
Dimensions: Not specified
Operating Temp: Not specified
Power Consumption: ≤300 mA at 5.0 V DC
Input Signal: 0-20 mA DC (transmitter power supported)
Input Resistance: 250 Ω
Allowable Input Current: ≤40 mA DC
Transmitter Power Supply: 25.0 to 25.5 V DC (≤60 mA DC limit)
Auxiliary Voltage Output: 1 to 5 V DC; ≤1 Ω output resistance; ≥10 kΩ load resistance; shared system ground
Square Root Extraction: Available by specification
Accuracy Rating: Voltage input ±4 mV; Current input ±16 µA; Auxiliary output ±12 mV
Effect of Ambient Change: 10 deg C → Voltage input ±4 mV and ±0.15 % of value; Current input ±32 µA; Auxiliary output ±24 mV
Data Update Period: 50 ms
Signal Insulation: Input signals insulated between systems
Withstanding Voltage: 1500 V AC/min
Installation: I/O Module Nest
Wiring: M4 screw terminal connection
Input Signal Settings: Configurable via software
The AAM11B supports integration with 4-20 mA HART loop protocol, enabling deterministic current and voltage signal acquisition. Input signals are insulated between systems with 1500 V AC/min withstand capability. Auxiliary voltage output provides stable reference supply, while square root extraction can be enabled via software for flow signal processing.
Q: Can the AAM11B provide power to connected transmitters? A: Yes, the module supplies 25.0 to 25.5 V DC with a current limit of 60 mA DC.
Q: How does ambient temperature variation affect measurement accuracy? A: A 10 deg C change results in ±4 mV drift for voltage input, ±32 µA drift for current input, and ±24 mV drift for auxiliary output.
Q: Is square root extraction available for flow measurement signals? A: Yes, square root extraction can be specified via software configuration.
Install the module securely into the I/O Module Nest.
Connect wiring to terminal blocks using M4 screws with proper torque.
Maintain shield grounding at a single point to prevent ground loops.
Separate signal wiring from high‑voltage cabling to minimize interference.
Configure input signal ranges and square root extraction via software before commissioning.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.