Sale
| Color / Pattern |
|
| Power Source |
|
| Communication Protocols |
|
| Controller Design |
|
The Yokogawa AAI543-H00/K4A00 drives 16 channels of 4 to 20 mA signals to field devices such as control valves and actuators. This module facilitates advanced asset management by supporting digital communication via the HART protocol. We provide this unit as 100% Brand New and Original equipment, ensuring seamless integration into your CENTUM VP distributed control system.
AAI543: 16-Channel Analog Output Module (4 to 20 mA).
-H: Integrated HART digital communication protocol.
0: Standard type (Note: "0" indicates standard switch-over response with explosion protection).
0: Basic type specification.
K4A00: Factory-installed KS Cable Interface Adapter for AEA4D Terminal Board connection.
Output Channels: 16 isolated channels.
Signal Range: 4 to 20 mA DC.
Update Period: 10 ms for rapid control loop response.
Load Resistance: Supports loads from 0 to 750 Ω.
Dielectric Strength: 1500 V AC isolation between output and system circuits.
Diagnostic Feature: Circuit-open detection activates when current drops below 0.65 mA.
Power Draw: 230 mA at 5 V DC and 540 mA at 24 V DC.
The AAI543-H00/K4A00 streamlines complex automation tasks by allowing both analog control and digital diagnostics over the same pair of wires. The 16-channel high-density configuration maximizes I/O rack efficiency, reducing the physical footprint of your control cabinets. Its robust isolation protects the system backplane from field surges, while the integrated K4A00 adapter provides a standardized interface for AEA4D terminal boards. This setup eliminates the risks of manual wiring errors and accelerates the commissioning of final control elements.
What is the primary function of the HART protocol in this module?The HART protocol allows the CENTUM VP system to overlay digital information on the 4-20 mA signal. This enables you to perform remote device configuration, monitor valve status, and access multi-variable data without extra wiring.
How does the circuit-open detection work?The module constantly monitors the output loop. If it detects a current flow below 0.65 mA, it flags a "Circuit Open" error to the system, helping maintenance teams pinpoint broken wires or failed actuators instantly.
Can I use this module for redundant configurations?Yes. The AAI543 series supports dual-redundant operation. In this setup, two modules work in parallel to ensure that a hardware failure does not interrupt the control signal to your field devices.
Does the K4A00 adapter come pre-installed?Yes, the K4A00 designation confirms that the module includes the KS Cable Interface Adapter (Model ATK4A-00) already mounted, allowing for immediate connection to your terminal boards using KS1 cables

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.