Configured for AC output actuation in FLEX I/O systems, the Allen Bradley 1794‑OA16 (1794‑OA16 digital output module) provides direct electrical switching across sixteen nonisolated output points within approved terminal base assemblies.
| Parameter | Specification |
|---|---|
| Model | 1794‑OA16 |
| Brand | Allen Bradley |
| Origin | USA |
| Weight | Not specified |
| Dimensions | Not specified |
| Operating Temp | 0 to 55 deg C (surrounding air) |
| Power Consumption | Max 4.7 W @ 0.5 A |
| Core Performance Indicators | 16 AC outputs, 74–132 VAC output range, 250 mA per point (4.0 A total), 7 A surge capability, 1.5 V drop @ 0.5 A, 80 mA Flexbus current, basic insulation field‑to‑backplane |
Within FLEX I/O architectures, the 1794‑OA16 participates in deterministic backplane bus communication velocity governed by the Flexbus interface. The module’s 80 mA backplane draw and nonisolated output structure allow predictable I/O density scaling when combined with other FLEX modules. Output propagation timing remains consistent across high‑channel‑count racks, ensuring stable scan cycles under mixed AC and DC module configurations. Firmware flash compatibility is maintained across standard FLEX adapters without requiring module‑specific revisions.
Q: Can the 1794‑OA16 be mounted on any FLEX terminal base A: It must be installed on approved bases: 1794‑TBN, 1794‑TBNF, 1794‑TB2, 1794‑TB3, 1794‑TB3S, 1794‑TBKD, 1794‑TBNK, 1794‑TBNFK, 1794‑TB3K, or 1794‑TB3SK.
Q: Are individual output channels isolated A: No. Channels are nonisolated; isolation exists only between field side and backplane.
Q: What is the maximum surge current capability A: 7 A for 40 ms, repeatable every 8 seconds.
Alternate wiring when using 0.5 A loads to avoid adjacent high‑current outputs. Maintain separation between AC output conductors and low‑level signal wiring. Verify terminal base screws are tightened according to base specifications. Ensure environmental conditions meet vibration, shock, humidity, and contamination limits before commissioning. Avoid routing AC conductors near high‑frequency drives to reduce induced oscillation on output waveforms.

Quick dispatch from our global inventory to reduce downtime and ensure uninterrupted operations.
All parts are sourced from reputable manufacturers and undergo thorough quality checks.
Extensive stock of industrial automation and discontinued parts, ready for immediate shipment.
Every product — including obsolete items — is covered by a 12-month warranty and 30-day return guarantee.
All product names, trademarks, brands, and logos mentioned on this website are the property of their respective owners.These names and trademarks are used for identification and reference purposes only.We are an independent supplier of industrial automation spare parts.We are not an authorized distributor, dealer, or representative of any manufacturer.Products supplied may include surplus inventory or unused items.We do not claim any affiliation with or endorsement by the original manufacturers.