{"product_id":"ge-ds200lppag1aaa-line-protection-panel-board","title":"GE DS200LPPAG1AAA Line Protection Panel Board","description":"\u003cp\u003eThe \u003cstrong\u003eGE DS200LPPAG1AAA\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eDS200LPPAG1\u003c\/strong\u003e Line Protection Panel Board, operates as a dedicated hardware component for AC line monitoring and signal filtering within Mark V Turbine Control System platforms.\u003c\/p\u003e\n\u003ch3\u003eSuffix Breakdown \u0026amp; Model Matrix\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eCode\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eDS200LPPA\u003c\/td\u003e\n\u003ctd\u003eBase Line Protection Panel Board\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eG1\u003c\/td\u003e\n\u003ctd\u003eRevision Group 1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAAA\u003c\/td\u003e\n\u003ctd\u003eRevision Level\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eDS200LPPAG1AAA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003eNot specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eStandard PCB form factor\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003eIndustrial ambient\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eSystem backplane nominal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e200 - 600 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eIndustrial Control \u0026amp; Firmware Characteristics\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eFirmware Flash Compatibility\u003c\/strong\u003e: The DS200LPPAG1AAA PCB operates within the fixed-logic architecture of the Mark V Speedtronic system. Parameter configuration and diagnostic status are managed through the system control panel menu; firmware updates are handled via serial interface upload\/download protocols between the control cabinet and a connected workstation.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eBackplane Bus Communication Velocity\u003c\/strong\u003e: The board interfaces with the drive backplane through designated terminal blocks, maintaining signal synchronization for turbine protection monitoring. Data transit velocity is determined by the system processor scan time and the hardwired nature of the protective circuitry.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eI\/O Density Scaling\u003c\/strong\u003e: The board utilizes seven configurable jumpers (JP1-JP7) and two terminal blocks to manage line protection signals. This discrete hardware configuration is optimized for the specific voltage range of 200 - 600 VAC, distinguishing it from the LPPB variant designed for higher voltage applications.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003eQ: What is the technical difference between an LPPA and LPPB board?\u003c\/p\u003e\n\u003cp\u003eA: The LPPA board (e.g., DS200LPPAG1AAA) is designed for system input voltages ranging from 230-600 VAC. The LPPB board is utilized for higher voltage applications ranging from 601-1500 VAC.\u003c\/p\u003e\n\u003cp\u003eQ: How is the physical replacement of the PCB performed?\u003c\/p\u003e\n\u003cp\u003eA: Ensure the drive is fully de-energized and all capacitors are discharged. Disconnect cables by grasping the connector body—not the wires—to remove from stab terminals. Release the board by squeezing the locking tabs on the four standoffs.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eStatic Handling\u003c\/strong\u003e: This PCB contains sensitive logic and protective components. Utilize a grounded wrist strap and ESD-safe mat during installation to prevent damage to integrated circuit paths.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eJumper Configuration\u003c\/strong\u003e: Verify settings for JP1 through JP7 before commissioning. These jumpers manage specific protection functions: JP1-JP3 (blown fuse indication), JP4\/JP7 (analog ground current sensing), JP5 (bridge voltage), and JP6 (SCR ripple filter).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWiring Integrity\u003c\/strong\u003e: When connecting signal wires to the terminal blocks, ensure wire gauge compatibility and confirm that all connections are secure. Avoid excessive mechanical strain on the board assembly during cable routing.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDiagnostic Verification\u003c\/strong\u003e: Post-installation, access the system diagnostic menu via the control panel keypad to confirm the health status of the board. Record baseline parameters before and after repairs to verify correct operation of the turbine control protection loop.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":48177361322174,"sku":"DS200LPPAG1AAA","price":650.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0725\/1145\/5422\/files\/screenshot_2026-07-20_11-23-03.png?v=1784517903","url":"https:\/\/www.autooiltech.com\/products\/ge-ds200lppag1aaa-line-protection-panel-board","provider":"AutoOilTech Limited","version":"1.0","type":"link"}